Page 21

Advertising
background image

Preparing for installation

Issue 2.0 June 2004

21

Service access specifications

Environmental specifications

For the most reliable system operation:

The room must have sufficient air conditioning capacity to support the cooling needs of
the entire system.

The air conditioning system must have controls that prevent excessive temperature
changes.

Do not turn on the computer until it has acclimated to the room temperature for at
least 24 hours.

Follow the guidelines in the table below for temperature, humidity, and altitude limits for
units in operation and for units that are not in operation (that is, units that are in transit or in
storage).

Parameter

English value

Metric value

Front

36 inches

91 centimeters

Rear

36 inches

91 centimeters

Left

36 inches

91 centimeters

Right

36 inches

91 centimeters

Parameter

Operating

(in service)

Nonoperating

(not in service)

Temperature

41°F to 95°F (5°C to 35°C)
IEC 68-2-1, 68-2-2

-4°F to 140°F (-20°C to 60°C)
IEC 68-2-1, 68-2-2

Humidity

(max)

20% to 80% RH
noncondensing; 27°C max wb
IEC 68-2-2, 68-2-3

93% RH
noncondensing at 40°C
IEC 68-2-2, 68-2-3

Altitude (max)

10,000 feet (3 kilometers)
IEC 68-2-40, 68-2-41

40,000 feet (12 kilometers)
IEC 68-2-40, 68-2-41