Gold Solo Hornet Installation Guide (EtherCAT and CAN) Technical Specifications
MAN-G-SOLHORIG-EC (Ver. 1.009)
84
5.5.2.
Digital Input Interfaces – PLC Mode
Feature
Details
Type of input
Optically isolated
Input current for all inputs
Iin = 2 mA @ Vin = 12 V
High-level input voltage
12 V < Vin < 30 V
Low-level input voltage
0 V < Vin < 7 V
Minimum pulse width
>250 µsec
Execution time (all inputs):
the time from application of voltage
on input until execution is complete
0<T< 250 µsec
High-speed inputs – 1 – 6 minimum
pulse width, in high-speed mode
T > 5 µsec if the input functionality is set to
latch/capture (index/strobe).
Notes:
•
Home mode is high-speed mode and can be
used for fast capture and precise homing.
•
Highest speed is achieved when turning on
optocouplers.
Figure 36: Digital Input Schematic
Capture with differential input
Port A, Port B Index
T > 0.1 µsec if the differential input functionality is
set to touch probe/capture (index/strobe).