OTe Instruction (Output energize)

This instruction is used to turn on an output or a bit when rung conditions are true. A typi-

cal output would consist of a relay or an indicator light. OTE instructions are reset when rung

conditions become false or the program is stopped and restarted.
The OTE instruction executes in 3.1µs and requires 38 bytes.
Following is a list of the data points that may be used with OTE instructions:

Relay outputs
Ladder bits

OTL Instruction (Output Latch)

This instruction is used to latch an output or a bit when rung conditions are true. The output

will remain latched even if rung conditions become false. A latched output (OTL) can only be

turned off using the OTU (Output unlatch) instruction.
The OTL instruction executes in 3.1µs and requires 42 bytes.
Following is a list of the data points that may be used with OTL instructions:

Relay outputs
Ladder bits

OTU (Output Unlatch)

This instruction is used to turn off a latched output or bit when rung conditions are true.

Thereafter, the output or bit remains off, regardless of the rung condition, until it is turned

on (typically by an OTL instruction in another rung). The instruction executes in 3.1µs and

requires 42 bytes.
Following is a list of the data points that may be used with OTU instructions:

Relay outputs
Ladder bits