Analog output wiring information – Sensaphone SCADA 3000 Users manual User Manual

Page 273

Advertising
background image

26-5

Chapter 26: Analog Output Module

Figure 7: Correct bus termination

ANALOG OUTPUT WIRING INFORmATION

The analog output module has four independent outputs which can be configured to produce

either 4–20mA, 0–20mA or 0–10V. The output type is selected using the jumpers (J8–J11)

above the terminal strip. The output types must be set in pairs. Jumper pair one affects outputs

0 and 1, and pair two affects outputs 2 and 3. This allows you to set, for example, outputs 0 and

1 to 4–20mA, and outputs 2 and 3 to 0–10V. The table below shows how to set the jumpers for

each output type.

Outputs 0 & 1 Outputs 2 & 3

Type

Jumper Settings

Type

Jumper Settings

4–20mA J8: 4–20, J10: mA

4–20mA J9: 4–20, J11: mA

0–20mA J8: 0–20, J10: mA

0–20mA J9: 0–20, J11: mA

0–10V

J8: 0–20, J10: V

0–10V J9: 0–20, J11: V

When configured for 4–20mA or 0–20mA, each output can drive a maximum of 1000 Ohms.

The output current is sourced directly from the module. No external loop power is required.

When configured for 0–10V, be sure to drive only high impedance loads to minimize errors. A

typical circuit connection diagram is shown below.

Figure 8: Wiring diagram

The output wiring terminals are designed to accept #14AWG to #24AWG stranded wires.

For short distances you may use ordinary 2-conductor cable. Note that if the output device is

located far from the module or if you are running cable in an electrically noisy environment,

you should seriously consider using shielded cable. This will shield the signal from electrical

interference thereby preventing false readings and/or damage to the module. If you are using

shielded cable, connect the shield to the EG pin on the module. To minimize electrical noise

coupling between I/O lines, follow the guidelines listed below for routing your wires:

• Route the power supply and communications cables to the module by a sepa-

rate path from wiring to I/O devices. Where paths must cross, their intersection

should be perpendicular.