Chapter 2: Quick Start Guide

Figure 5. Main Programming form

Select the Programming pull-down menu.
Choose “System” to bring up the system form.

Figure 6: System form

System Information

Both the Unit Name and ID Number should be the same as those you assigned on the New

Unit form.

Dialout Settings

1. Dial Method: Can be either tone or pulse. Default setting is Tone.
2. Dialing Prefix: for E-Mail prefixes only. If you need to dial a “9” to get an out

side line before dialing an email server number, enter that here. For other dialout

prefixes see the “Destinations” section of the manual.

3. Voice repetitions: The number of times the SCADA 3000 repeats alarm messages

per call. Default setting is 2.

4. Maximum calling rounds: the number of times a SCADA 3000 will dial through

your list of destinations to deliver its messages. Default is 100.

5. Alphanumeric Pager Speed: Default setting is 1200 Baud

Call Reception Settings

1. Rings till Answer: the number of times the SCADA will let the phone ring before

answering an incoming call. Default is 1 ring; range is 1-20 rings.

2. Carrier Wait Time: The amount of time SCADA will wait for a modem

connection when receiving an incoming call. Default is 60 seconds; range is 0 to

90 seconds.

Note: Don’t set this time too short, or a modem connection may never be established.