I/o programming, I/o programming -4 – Sensaphone SCADA 3000 Users manual User Manual

Page 36

Advertising
background image

2-4

SCADA 3000 User’s Manual

3. Online Timeout: Automatically logs you off if there are no communication

requests from the computer within the specified time period. The default

setting is 4 minutes. Range: 0–255, with “0” representing a disabled setting.

Click OK.

I/O Programming

Click on the first of the three Motherboard and Module I/O programming buttons

to bring up the I/O form for the first 8 inputs, the second button for the next 8 inputs and the

third button for the 8 outputs.

Figure 7: I/O Points

The form above shows the first eight inputs on the main unit, 0–7, retrieved by clicking on the

first of the three buttons.
Click the “I/O Setup” button to open the setup form. Here you assign each input a name, a

type, and the units of measurement applying to that type.
To set the Low and High values for inputs, and the calibration factor if any, click on the “Table

and Cal” button.
Click on OK to close the form once you’ve programmed your inputs.