SCADA 3000 User’s Manual

Instructions:

1) Click on the Select HEX file button.
2) Open the SCADA 3000 firmware folder.
3) The two HEX files should appear. Click on the Control HEX file and click

Open.

4) In the Select a Processor field, click “Control ROM.”
5) Click the begin Upload button. After a few seconds the upgrade will begin.

When its 100% finished, click on the Logout button. During the Upload pro-

cess, the LCD will display “Uploading Control Flash Programming.” After

the upload process, the display will change to “Reprogramming Control Flash

Memory.” This will take about one minute, after which the display will return

to its normal scrolling messages. Do not disrupt the unit until the reprogram-

ming message has disappeared.

6) Go online with the unit again.
7) Click on Diagnostics>Flash Upgrade from the main menu again.
8) Click on the Select HEX file button.
9) Open the SCADA 3000 firmware folder.
10) The two HEX files should appear. Click on the Comm HEX file (communica-

tions) and click Open.

11) In the Select a Processor field, click “Communications ROM.”
12) Click the begin Upload button. After a few seconds the upgrade will begin.

When its 100% finished, click on the Logout button. During the Upload pro-

cess, the LCD will display “Uploading Communications Flash Programming.”

After the upload process, the display will change to “Reprogramming

Communications Flash Memory.” This will take about one minute, after which

the display will return to its normal scrolling messages. Do not disrupt the unit

until the reprogramming message has disappeared.


The Flash upgrade is now complete. You may go back online and restore your programming.