SCADA 3000 User’s Manual

Figure 8: Wiring a Dry Contact Sensor

1OK Thermistors

The Universal Input Module is compatible with 10K thermistors that match the curve data

listed in the table in Appendix A. The monitoring temperature range of the 10K thermistor is

-80 to 300ºF (-62º to 149ºC). These devices can be connected directly to the input terminals

without regard for polarity. Choose an input and connect the wires to the corresponding screw

terminals for that input. The configuration jumper should be set to the TMP/DRY position.

The figure below shows how to connect a dry contact sensor:

Figure 9: Wiring a Thermistor

Analog Voltage Output Transducers (0–5VDC)

The Universal Input Module is compatible with transducers that produce an analog output of

0 to 5VDC. You can program High and Low table values from the SCADA 3000 Software to

scale the signal to the appropriate values.
Analog voltage output devices can be connected directly to the input terminals but be sure to

following the polarity markings on the module. Choose an input and connect the wires to the

corresponding screw terminals for that input. The configuration jumper should be set to the

storage position as indicated in the diagram below: