Appendix h: troubleshooting – Sensaphone SCADA 3000 Users manual User Manual

Page 293

Advertising
background image

H-1

Appendix H: Troubleshooting

Appendix H: TROUBLeSHOOTING

Why does my SCADA 3000 begin dialing as soon as I turn it on?

• SCADA 3000 will dial out for only two reasons, to deliver an alarm message or a report.

If the alarm LED is blinking, an unacknowledged alarm exists and SCADA 3000 is trying to

deliver an alarm message. If the alarm LED is either off or on steady, the unit is dialing out to

deliver a report.
• The shunt for setting your input type may be in the wrong position, causing a false alarm

condition. Check that it is in the correct position for the type of sensor you’re using.
• The unit might have an unacknowledged alarm for which it’s still trying to dial out and

deliver its message. Even though the condition no longer exists, the unit will attempt to deliver

its message until it is finally acknowledged. If this is the case, either go on-line with a PC and

clear the alarm; or call the unit back and give the Touch-Tone acknowledgment code. You can

also plug a telephone into the Voice Record jack and give the Touch-Tone acknowledgment

code.
On site, you can also check and acknowledge an alarm via the Keypad.

1) Press the MENU button, arrow-down to the Alarms category, and press

ENTER.

2) Press the down-arrow key until you reach the alarm you need to acknowledge.

Press ENTER.

3) Press the down-arrow key until the LCD displays Acknowledge Alarm. Press

ENTER and the alarm will be acknowledged. If you continue to press the down-

arrow key, the Acknowledge All option will be displayed. If you press ENTER

while this message is showing, all alarms will be acknowledged.

Why can’t I connect with my SCADA 3000?

Having trouble connecting locally
Some common causes:
• SCADA 3000 is connected to your PC’s parallel port (LPT1) instead of a serial COM port

(COM1, COM2, etc.).
• SCADA 3000 is connected to the wrong serial COM port. Most PCs have multiple serial

ports. Make sure the port connected to the SCADA 3000 unit is the same port shown the

UNIT DATABASE form.
• Check that the SCADA 3000 software has configured the COM port as a direct Serial Port

connection. Click Comm>Setup from the Sensaphone Control Center Main Menu. Click the

appropriate Comm Port tab and check that the port is Enabled, the Type is set to Serial Port, and

the Port Baud Rate is set to 38400.
Having trouble connecting using a modem
If your modem won’t dial at all:
• Make sure that your modem is connected to a serial COM port on your PC, not a parallel

(LPT) port.
• Check that the PC’s COM port connected to the modem is the same port shown on the

UNIT DATABASE form.

Advertising