5-5

Chapter 5: Input Wiring

Figure 7: 0-5V Circuit diagram

4–20mA Current Loop Transducers

The inputs on the SCADA 3000 are compatible with transducers that produce an analog out-

put current of 4 to 20mA. Analog 4–20mA output devices sometimes require a 24VDC power

supply to operate. The SCADA 3000 provides a built-in 24VDC power supply for this pur-

pose. The 24VDC power supply has enough capacity to power up to sixteen 4–20mA devices.

Follow the wiring diagrams below for connecting a 4–20mA device. The configuration jumper

should be set to the 4–20mA position as indicated in the following diagrams:

Figure 8: Wiring a 4

20mA device using the built-in 24 VDC supply.

The shunt set to the 4-20mA position is reflected in the following circuit diagram.

Figure 9: 4

20mA Circuit diagram