Tables and calibration, Outputs, Tables and calibration -12 uaf -12 outputs -12 – Sensaphone SCADA 3000 Users manual User Manual

Page 80

Advertising
background image

10-12

SCADA 3000 User’s Manual

TABLeS AND CALIBRATION

To program the custom table values and calibration, click the Table and Cal button. The fol-

lowing screen will appear.

Figure 6: I/O table form

You can set up custom tables for 0–5 volt and 4–20mA input types so that the values are read

in engineering units. For example, say you have a 4–20mA transducer connected to a 400 inch

tank and the transducer puts out 4mA when the tank is empty and 20mA when the tank is full.

If you enter a table low value of 0 and a table high value of 400, the reading displayed by the

SCADA 3000 will be in inches, indicating the amount of material in the tank.
The calibration factor is a multiplier used to correct errors in your system. When set to 1.000

the calibration factor has no effect on the reading. To compensate for an input that is reading

high, set the calibration just below 1.0, to a number like 0.98. To compensate for an input that

is reading too low, try entering 1.02 for the calibration factor. You can continue to adjust the

calibration by trial and error until the reading is accurate or you can compute the percent error

directly and enter the calibration factor accordingly.

UAF

Inputs and Outputs can be referenced within the SCADA 3000 using the individual channel’s

physical address. The physical address is referred to as the UAF, or Universal Address Format.

The identifying UAF for each channel is listed on the left column of all screens on the I/O

form. The UAF format is used extensively in the SCADA 3000 for reading, writing, referenc-

ing or assigning parameters. They are required when programming Alarms, Voice messages,

Datalogging, PID control, C-programs, and Ladder programs. See “Universal Address Format”

earlier in this chapter for more detailed information on the UAF format.

OUTPUTS

The SCADA 3000 has 8 relay outputs on the main board which can be controlled either manu-

ally or automatically via C or Ladder programs. To access the Outputs programming form,

click on the Motherboard Outputs button from the toolbar. The following form will appear: