Chapter 2, Storage and operation conditions, Ce compliance – Rockwell Automation 160 SSC Series C FRN 7.xx User Manual

Page 13: Installation, Clearances, Debris label, Installation and wiring, Clearances -1 debris label -1, Chapter

Advertising
background image

Chapter

2

Installation and Wiring

Storage and Operation Conditions

Follow these recommendations to prolong drive life and performance:

• Store within an ambient temperature range of –40

° to +85°C.

• Store within a relative humidity range of 0% to 95%, non-condensing.

• Protect the cooling fan by avoiding dust or metallic particles.

• Avoid storing or operating the drive where it could be exposed to a corrosive

atmosphere.

• Protect from moisture and direct sunlight.

• Operate at an ambient temperature range of 0

° to +50°C.

CE Compliance

Refer to Appendix C.

Installation

Mount the drive on a flat, vertical and level surface. See Chapter 1, Figure 1.3 for
mounting orientation.

Choose an installation method:

• Install with screws. Recommended screw size is listed in the table below.

The appropriate drilling template for your drive is provided in Appendix B.

• Install on 35 mm DIN Rail. This mounting method is not available on

4.0 kW (5 HP) three phase or 1.5 kW (2 HP) single phase models.

See Appendix B for details on drive dimensions and weights.

Clearances

Maintain 12.5 mm (0.5 in.) clearance at the top, bottom, and front of all drives.
Clearance requirements between units varies by model.

• 2.2 kW (3 HP) 230V/460V Drives

Provide a minimum of 8.5 mm (0.33 in.) clearance between units.

• All Other Drive Ratings

No clearance is required between units.

Debris Label

The drive is shipped with a paper debris label attached to the top side of the plastic
housing to cover the cooling vents. Leave the debris label attached during drive
installation to protect against debris falling through the vents of the drive housing.
To assure proper drive operation, you must remove label before applying power.

Description

Metric

English

Minimum Panel Thickness (14 GA)

1.9 mm

0.0747 in.

Mounting Base Screws

m4 x 0.7

# 8-32

Mounting Torque

1.13 – 1.56 Nm

10 – 14 lb.-in.

ATTENTION: After system installation, remove the debris label
from unit. Failure to remove this label may result in overheating or
nuisance tripping.