Parameters and Programming

5-13

[Preset Frequency 0-7]

The programmed value sets the frequency that the drive outputs when selected.
Refer to Chapter 2, Figure 2.21 for the Preset Speed model control wiring diagram.

0.0/240.0

0.1 Hz

See Table

69

[Accel Time 2]

Time for the drive to ramp from 0.0 Hz to P33 - [Maximum Frequency]. The rate
is linear for any increase in command frequency unless P53 - [S-Curve] is set to
a value other than 0. Setting this to 0.0 gives 0.1 seconds acceleration with the
initial current limit turned off. This allows quicker acceleration times for low inertia
systems. For medium to high inertia systems, the minimum value should be 0.1.

0.0/600.0

0.1 Sec.

20.0
Seconds

70

[Decel Time 2]

Time for the drive to ramp from P33 - [Maximum Frequency] to 0.0 Hz. The rate
is linear for any decrease in command frequency unless P53 - [S-Curve] is set
to a value other than 0.

Minimum deceleration time must be set based on the applied motor size.

To guard against premature drive failure, do not set P31 - [Decel Time 1] or
P70 - [Decel Time 2] below the minimum value listed in the table below.

/600.0

0.1 Sec.

20.0
Seconds

Program Group

No.

Parameter Name/Description

Min./Max.
Range

Units

Factory
Default

Preset Speed Model Only

Signal Follower
Model Only

(Input Mode 8)

Preset Freq.

Default

TB3-4
(SW3)

TB3-2
(SW2)

TB3-1
(SW1)

TB3-8
(SW2)

TB3-2
(SW1)

Accel

Decel

61

Preset 0

3.0 Hz

0

0

0

0

0

P30
[Accel Time 1]

P31
[Decel Time 1]

62

Preset 1

20.0 Hz

0

0

1

0

1

63

Preset 2

30.0 Hz

0

1

0

N/A

N/A

64

Preset 3

40.0 Hz

0

1

1

N/A

N/A

65

Preset 4

45.0 Hz

1

0

0

1

0

P69
[Accel Time 2]

P70
[Decel Time 2]

66

Preset 5

50.0 Hz

1

0

1

1

1

67

Preset 6

55.0 Hz

1

1

0

N/A

N/A

68

Preset 7

60.0 Hz

1

1

1

N/A

N/A

When using P46 - [Input Mode] setting 4, the Accel and Decel times are selected by providing an input to TB3-8.
See Chapter 2, Figure 2.12 for additional information.

230 and 460V
Motor Sizes

Minimum Deceleration Settings

4.0 kW (5 HP)

0.7 seconds

2.2 kW (3 HP)

0.6 seconds

1.5 kW (2 HP)

0.2 seconds

0.75 kW (1 HP)

0.1 seconds

0.55 kW (0.75 HP)

0.1 seconds

0.37 kW (0.5 HP)

0.1 seconds

This parameter applies only to the Preset Speed model.