Specifications

A-3

Control Features

PWM Algorithm

Sine Weighted PWM with Harmonic Compensation

Switching Device

IGBT

V/Hz Ratio

Programmable

Carrier Frequency

Adjustable from 2 to 8kHz in 100 Hz Increments (Factory Default is 4kHz)

DC Boost

Adjustable — Select from a Family of Boost Curves

Current Limiting

Software Controlled, Coordinated for Drive and Motor Protection — Programmable
from 1 to 180% of Drive Output Current

Motor Protection

I

2

t Overload Protection — 150% for 60 Seconds, 200% for 30 Seconds

Overload Pattern #0

Flat Response Over Speed Range (No Speed Compensation)

Overload Pattern #1

Speed Compensation Below 25% of Base Speed

Overload Pattern #2

Speed Compensation Below 100% of Base Speed

Accel/Decel Time(s)

0.1 to 600 Seconds

S-Curve Accel/Decel Time(s)

0 to 100% of Accel/Decel Time — Not to Exceed 60 Seconds

Stopping Modes

4 Programmable Modes:
Ramp to Stop —

0.1 to 600 Seconds

Coast to Stop —

Stops All PWM Output

DC Injection Braking — Applies DC Voltage to the Motor for 0 to 25 Seconds
DC Injection Braking with Auto Stop

Protective Features

Overcurrent

Programmable limit, 200% of Hardware Limit, 300% of Instantaneous Fault

Excessive Temperature

Embedded Temperature Sensor Trips if Heatsink Temperature Exceeds 95

°C

Over/Under Voltage

DC bus voltage is monitored for safe operation.

• For 200-240VAC input drives, the overvoltage trip occurs at a bus voltage of 400VDC

(equivalent to a 290VAC incoming line voltage).

• For 380-460VAC input drives, the overvoltage trip occurs at a bus voltage of 800VDC

(equivalent to a 575VAC incoming line voltage).

• For 200-240VAC input drives, the undervoltage trip occurs at a bus voltage of

210VDC (equivalent to a 150VAC incoming line voltage).

• For 380-460VAC input drives, the undervoltage trip occurs at a bus voltage of

390VDC (equivalent to a 275VAC incoming line voltage).

Control Ride Through

Minimum Ride Through is 0.5 Seconds — Typical Value is 2 Seconds

Ground Short

Any Output Phase to Ground Short

Faultless Ride Through

100 Milliseconds

Output Short Circuit

Any Output Phase to Phase Short

Programming

Programmer

Optional — Removable Program Keypad Module

Display Type

6 Character LED — Two Digit Parameter Number and Four Digit Value

Keypad Controls

Speed, Run, Stop and Direction