Installation and Wiring

2-3

Terminal Block Wiring

Terminal Block Wiring Detail

Figure 2.2

Specifications

Terminal Block TB1 and TB2 Wiring Specifications

Table 2.A

➊ For single phase input applications, connect the AC input power to input terminals S (L2) and T (L3).
See Table 2.B for minimum recommended branch circuit protective devices.
➌ Bulletin 160 Drives are UL Listed (see Appendix A for details) as motor overload protective devices

(IEC Class 10 overload). An external overload relay is not required for single motor applications
as long as the Drive kW (HP) rating is less than three times larger than the motor kW (HP) rating.

➍ Each terminal supports up to 2 wires of approved gauge.

Model

Screw Size

Max./Min. Wire Size

mm

2

(AWG)

Max./Min. Torque
Nm (lb.-in.)

4.0 kW (5 HP)

M4

5.26 – 3.31 (10 – 12)

1.35 – 0.90 (12 – 8)

All Other Ratings

M4

3.31 – 0.82 (12 – 18)

1.35 – 0.90 (12 – 8)

Required Branch

Circuit Disconnect

Branch Circuit
Protective Device

BR+

T/L3

S/L2

R/L1

BR–

DC+

W/T3

V/T2

U/T1

DC–

Ground Terminal/Protective Earth

Terminal Block TB1

Terminal Block TB2

Motor