Overview of Parameters

This chapter describes both Display and Program parameters. Display parameters
are read only (they cannot be programmed), while Program parameters can be
changed to fit your motor control requirements. A Program Keypad Module,
Remote Keypad Module or CopyCat Keypad Module allow you to view or change
parameters. Communication Modules (RS1, DN1 or DN2) allow you to view or
change parameters with an additional device. A Ready/Fault Indicating Panel
cannot be used to view or change parameters. The table below describes which
parameters apply to the Preset Speed and Analog Signal Follower models

.

Some parameters pertain only to either the Analog Signal Follower or Preset Speed
model, not both.

Review the factory default settings. These parameters can be changed to meet your
specific application requirements with any of the following: Program Keypad
Module, Remote Keypad Module or CopyCat Keypad Module. The table below
provides a list of parameters that are frequently changed.

Commonly Changed Parameters

Table 5.A

Refer to the Programming Example on the next page for instructions.

Parameter Type

Analog Signal Follower Model
Parameter Numbers

Preset Speed Model
Parameter Numbers

Display

1 – 19

1 – 15, 17 – 19

Program

30 – 62, 65, 66, 69 – 76, 78 – 84

30 – 59, 61 – 73, 78 – 80

⇐ Indicates that parameter applies only to the Analog Signal Follower Model
⇐ Indicates that parameter applies only to the Preset Speed Model

Parameter

Setting

Default Setting

P30 - [Accel Time 1]

Desired accel time.

10.0 sec

P31 - [Decel Time 1]

Desired decel time.

10.0 sec

P33 - [Maximum Frequency]

Maximum frequency required.

60 Hz

P34 - [Stop Mode Select]

Desired stopping mode.

0

P35 - [Base Frequency]

Motor rated nameplate frequency.

60 Hz

P36 - [Base Voltage]

Motor rated nameplate voltage.

460V or 230V

P38 - [Boost Select]

Desired V/F boost setting.

2

P42 - [Motor Overload Current]

Motor nameplate Full Load Amps (FLA).

115%

P43 - [Current Limit]

Desired maximum output current.

150%

P46 - [Input Mode]

Desired control method.

0

P47 - [Output Configure]

Desired output relay function.

0

P56 - [Reset Functions]

Desired drive reset description.

0

P58 - [Internal Frequency]

Desired internal frequency.

60.0 Hz

P59 - [Frequency Select]

Desired frequency source.

0

P61 – P68 - [Preset Frequency 0-7]

Desired preset frequencies.

0-7

P74 – P76 - [Analog Input]

Desired analog input functionality.

0, 0.0, 100.0%