4-2

Start-Up

Yes

No

Ready/Fault Indicating Panel Procedure

If you are using a Program Keypad Module, verify that

the Clockwise LED is illuminated. If you are using a

Ready/Fault Indicating Panel, verify that the Reverse input to

TB3 is in the Open position.

P01- [Output Frequency] will display. If drive has been previously
powered up, a different parameter may display.
Important: To enable the Start and Reverse keys on the Program
Keypad Module, set P46 - [Input Mode] to 2 and cycle power (or
set P56 - [Reset Function] to 2). Refer to P56 in Chapter 5.

Program Keypad Module, Remote Keypad Module or

CopyCat Keypad Module Procedure

Set the frequency source to its minimum setting.

Issue a Stop command from the Program Keypad Module or TB3.

Issue a Start command from the Program Keypad Module

or TB3. Check the direction of motor rotation.

Drive fan will energize (some models).

If you are using a Program Keypad Module, verify that the

Clockwise LED is illuminated. If you are using a Ready/Fault

Indicating Panel, verify that the Reverse input to TB3 is in the

Open position.

Select P61 - [Preset Frequency 0] by removing all inputs to SW1,

SW2, and SW3 on TB3 (see Figure 2.21). The factory default

setting for P61 - [Preset Frequency 0] is 3 Hz.

Issue a Start command from the Program Keypad Module or

TB3. Drive fan will energize (some models).

Slowly increase the speed until the motor begins to turn.

Check the direction of motor rotation.

Issue a Stop command from the Program Keypad Module or TB3.

Direction of Motor Rotation Correct?

The green Ready indicator will illuminate.

Use inputs to TB3 to operate the drive.

Analog Signal Follower Model

Preset Speed Model

❶ Start-up is complete!

Disconnect and lock out all incoming power to

TB1 terminals R, S and T (L1, L2, and L3).

Switch any two of the three motor leads connected to TB2, terminals
U, V and W (T1, T2 and T3). Reconnect power. Check rotation.

continued from previous page

ATTENTION:

A DC Bus voltage may be present at the power

terminal blocks TB1 and TB2 for approximately three minutes after
power is removed from the drive.

❶ After successfully completing start-up, proceed to Chapter 5. If you need to change any factory

defaults, you will need a Program Keypad Module or other type of Communication Module.