Capacitive Current Coupling

AC coupling exists from motor cables to ground terminal/protective earth. The
current produced by this coupling is referred to as capacitive current. The drive
current is the combination of capacitive current and motor current. Because motor
current is monitored for overload protection, the table below lists the maximum
cable length recommendations that will assure a capacitive current error of less
than 15 percent.

Cable Length Recommendations — Capacitive Current

Table 2.F

➊ Not recommended for use above 4 kHz PWM Frequency.
➋ When using shielded cable at lightly loaded conditions, cable length recommendations for drives rated 0.75 kW (1 HP) and

below are 61 meters (200 feet).

➌ Not recommended for 230V applications.

380-460V
Ratings

kHz

Motor Cable Only

RWR at Drive

Reactor at Motor

Shielded

Unshielded

Shielded

Unshielded

Shielded

Unshielded

feet

meters feet

meters feet

meters feet

meters feet

meters feet

meters

4.0 kW
(5 HP)

2

350

107

600

183

300

91.5

600

183

400

122

600

183

4

425

130

600

183

350

107

600

183

450

137

600

183

8

475

145

500

152

450

137

500

152

2.2 kW
(3 HP)

2

360

110

600

183

280

85.4

600

183

400

122

600

183

4

375

114

600

183

275

83.8

600

183

400

122

600

183

8

400

122

500

152

400

122

500

152

1.5 kW
(2 HP)

2

300

91.5

550

168

275

83.8

600

183

300

91.5

600

183

4

300

91.5

550

168

275

83.8

600

183

300

91.5

500

152

8

325

99.1

500

152

350

107

500

152

0.75 kW
(1 HP)

2

200

61

375

114

200

61

425

130

225

68.6

400

122

4

225

68.6

375

114

200

61

425

130

225

68.6

375

114

8

250

76.2

375

114

225

68.6

400

122

0.55 kW
(0.75 HP)

2

180

54.9

350

107

180

54.9

375

114

180

54.9

350

107

4

180

54.9

350

107

180

54.9

375

114

180

54.9

350

107

8

180

54.9

350

107

180

54.9

350

107

0.37 kW
(0.5 HP)

2

100

30.5

325

99.1

100

30.5

350

107

100

30.5

300

91.5

4

100

30.5

325

99.1

100

30.5

350

107

100

30.5

350

107

8

100

30.5

325

99.1

100

30.5

350

107

200-240V Ratings

No Reactor

RWR at Drive

Reactor at Motor

0.37 to 4.0 kW
(0.5 to 5 HP)
2 through 8 kHz

Shielded

Unshielded

Shielded

Unshielded

Shielded

Unshielded

feet

meters feet

meters feet

meters feet

meters feet

meters feet

meters

525

160

600

183

525

160

600

183