Chapter 3, Features, Display mode – Rockwell Automation 160 SSC Series C FRN 7.xx User Manual

Page 33: Program mode, Program keypad module, Features -1, Display mode -1 program mode -1, Chapter

Advertising
background image

Chapter

3

Program Keypad Module

The Program Keypad Module is located on the front panel of the drive. This module
is only operational when it is installed directly on the drive.

Features

The Program Keypad Module provides the following features:

• 6-digit, 7-segment LED display

• Program Mode Indicator

• Five keys for programming and displaying drive parameters

• Three keys for control inputs to the drive

• Two directional LED indicators

Program Keypad Module

Figure 3.1

Display Mode

The drive always powers up in the Display mode. While in this mode you may
view all read only drive parameters, but not modify them.

Program Mode

You enter the Program mode by pressing the ESCape key. While in this mode,
you can edit Program Group parameters by pressing the SELect key. The Program
Mode Indicator will flash (see Figure 3.1) indicating the parameter value can be
changed. The Enter key (

↵) must be pressed to write the new value to memory.

Refer to Chapter 5 for programming steps.

Parameter Number Display
Indicates which Display or Program Group parameter is active.

Parameter Value/Fault Number
Displays the parameter value or fault code number.

Program Mode Indicator
Flashes when in program mode.

Control Inputs and Indicators
Direction, Start, Stop (Stop is always active).

Important:

To activate Direction and Start inputs, P46 - [Input Mode]
must be set to 2. Power must be cycled or P56 - [Reset
Functions] must be set to 2 for the change to take effect.

Advertising