Figure 2.4, Figure 2.5 – Rockwell Automation 160 SSC Series C FRN 7.xx User Manual

Page 24

Advertising
background image

2-12

Installation and Wiring

P46 Setting 0 - Three-Wire Control (Factory Default)

This input mode provides a typical three wire control function where a momentary
start input will command the drive to start.

Three-Wire control – Factory Default

Figure 2.4

➊ Start input can be a momentary input.

P46 Setting 1 - Two-Wire Run Forward/Run Reverse Control

This input mode provides a typical two wire control function where a maintained
Run Forward or Run Reverse input will provide both a directional and start
command to the drive. Opening the Run Forward or Run Reverse input will
command the drive to stop in accordance with the P34 - [Stop Mode] setting. The
stop switch (TB3-7 and 8) is not required but can be wired as an Auxiliary Stop if
desired.

Two-Wire Run Forward/Run Reverse control

Figure 2.5

Stop

56

7

8

Common

Reverse

Start

TB3

Note: A contact closure on
terminals 7 and 8 is required
for the controller to respond
to a Start/Run command.

Stop

56

7

8

Common

Run Forward

Run Reverse

TB3

Note: A contact closure on
terminals 7 and 8 is required
for the controller to respond
to a Start/Run command.