Parameters and Programming

5-11

51

[Restart Time]

Time between restart attempts.
If this parameter and P50 - [Restart Tries] are both set to zero, and P46 - [Input
Mode] is not set to 3, the auto fault clear feature is enabled. This feature
automatically clears overvoltage, undervoltage, and overtemperature faults 1
second after the fault condition is removed.
If this parameter is set to zero and P50 - [Restart Tries] is not zero, then the time
between restart attempts is 1 second.

0.0/300.0

0.1
Seconds

10.0
Seconds

52

[DB Enable]

Enables/disables external dynamic braking.
Setting “0” = Disable. Settings 1 through 100 = % duty cycle braking.

This parameter cannot be programmed while the drive is running.

0/100

Numeric
Value

0

53

[S-Curve]

Enables a fixed shape S-Curve. See formula below:

Formula:

S-Curve Time = Accel or Decel Time x S-Curve Setting

(in percent)

➊ See values below.

Example:

Accel Time = 10 Seconds
S-Curve Setting = 3
S-Curve Time = 10 x 0.3 = 3 Seconds

Important: Maximum S-Curve time is 60 seconds.

0/10

Numeric
Value

0

Program Group

No.

Parameter Name/Description

Min./Max.
Range

Units

Factory
Default

ATTENTION: The 160 Dynamic Brake Module is rated for 5%

duty cycle. Use of this package above 5% should not be used and

voids the UL rating of this device. When setting this parameter

to a value above 5% duty cycle, the resistor must be sized to avoid
overheating of the resistor package.

Accel Time

1/2 S-Curve

Time

1/2 S-Curve

Time

Enabled

Disabled

1/2 S-Curve

Time

1/2 S-Curve

Time

Decel Time

S-Curve Setting
0
1
2
3
4
5
6
7
8
9
10

= 0%
= 10%
= 20%
= 30%
= 40%
= 50%
= 60%
= 70%
= 80%
= 90%
= 100%