A-2

Specifications

All Drive Ratings

Table A.3

Input/Output Ratings

Output Voltage

Adjustable from 0 to Input Voltage

Output Frequency

Programmable from 0 to 240 Hz

Efficiency

97.5% Typical

Transient Protection

Standard 6 kV

Environmental Specifications

Enclosure

IP20

Ambient Temperature

0

°C to 50°C

Storage Temperature

–40

°C to 85°C

Relative Humidity

0 to 95% Non-Condensing

Vibration

1.0 G Operational — 2.5 G Non-Operational

Shock

15 G Operational — 30 G Non-Operational

Altitude

1,000 m (3,300 ft) without Derating

Control Inputs

Control Input Type

Dry Contact Inputs —

Drive has an internal 12V power supply that provides 10
mA typical current flow.

Alternate Inputs —

Accepts open collector/solid state inputs (sinking into the
drive) with maximum leakage current of 50

µA.

24V Inputs —

An optional 24V DC interface module allows use of 24VDC
sinking inputs (see ).

Start, Stop, Fwd/Rev

Configurable Inputs for Two- or Three-Wire Control

SW1, SW2, SW3

Preset Speed Model Only

Configurable Inputs for Control of 8 Preset Speeds and 2 Accel/Decel Times

Programmable Input

TB3-8 Can Be Configured to Select:
• Accel/Decel Times
• External Coast to Rest
• TB3 Control/Keypad or Communication Control

• Frequency Select
• Preset Speed

Approvals and Standards Compliance

Approvals

Designed to Meet These Standards

FCC Class A

➋ and B ➋, IEC 146-1-1, VDE 0871 and VDE 0875

Control Inputs — Analog Signal Follower Only

External Speed

Potentiometer

1K to 10K Ohms, 2 Watts Minimum

4 – 20 mA Analog Input

250 Ohms Input Impedance

–10 to +10VDC

Analog Input

100K Ohms Input Impedance

Control Output

Programmable Output

(Form C Relay Contact)

Resistive Rating: 0.4A at 125VAC — 0.2A at 230VAC — 2A at 30VDC
Inductive Rating: 0.2A at 125VAC — 0.1A at 230VAC — 1A at 30VDC

➊ Analog Signal Follower only.
➋ With external components.

UL

®

LIST

ED 966X

IND CONT EQ

UL508C

UL

®

LIST

ED 966X

IND CONT EQ

C

CSA 22.2

AS/NZS 2064.1:1992

EMC Directive 89/336

LV:

EN 50178, EN 60204

EMC: EN 61800-3, EN 50081-1, EN 50082-2