Parameters and Programming

5-7

38

[Boost Select]

Sets the boost voltage and redefines the Volts per Hz curve. Settings 0 – 8 can
provide increased torque at low frequency. Settings 9 – 12 are used to reduce
energy consumption.

0/12

Numeric
Value

2

39

[Skip Frequency]

Works in conjunction with P40 - [Skip Frequency Band] creating a range of
frequencies at which the drive will not operate continuously.

0/240

1 Hz

240 Hz

40

[Skip Frequency Band]

Determines the band around the P39 - [Skip Frequency] parameter. The actual
band width will be 2 times P40 - [Skip Frequency Band] - 1/2 the band above and
1/2 the band below. A value of zero will disable the skip frequency.

0/30

1 Hz

0 Hz

Program Group

No.

Parameter Name/Description

Min./Max.
Range

Units

Factory
Default

% [Base Frequency]

% [Base

Vo

ltage]

100

50

1/2 Base Volts

1/2

Base Freq.

9
10
11
12

0

50

100

1

8

See

Settings 1-8

Setting

Boost Voltage
(% of [Base Voltage])

0
1
2
3
4
5
6
7
8

0
2.5
5.0
7.5
10.0
12.5
15.0
17.5
20.0

Setting

Fan/Pump Curves

9
10
11
12

45.0
40.0
35.0
30.0

➊ Break Point Voltages in percent of [Base Voltage]

tu

pt

u

O

y

c

n

e

u

q

e

r

F

r

e

ll

o

r

t

n

o

C

Frequency

Time

Skip

Frequency

Setting

Command

Frequency

2 x P40

[Skip Freq Band]

Setting