Parameters and Programming

5-3

Display Group Parameters (Read Only)

This group of parameters consists of commonly viewed drive operating conditions
such as output frequency, output voltage, output current and frequency command.
All parameters in this group are read only.

Important:

The last user-selected Display Group parameter is saved when
power is removed and is displayed by default when power is
reapplied.

Display Group (Read Only)

No.

Parameter Name/Description

Min./Max. Range

Units

01

[Output Frequency]

Displays the output frequency at TB2 terminals U, V & W (T1, T2 & T3).

0.0/240.0

0.1 Hz

02

[Output Voltage]

Displays the output voltage present at TB2 terminals U, V & W (T1, T2 & T3).

0/Max Voltage

1 Volt

03

[Output Current]

Displays the output current present at TB2 terminals U, V & W (T1, T2 & T3).

0/2 x Drive Rated
Output Current

0.01A

04

[Output Power]

Displays the output power present at TB2 terminals U, V & W (T1, T2 & T3).

0/2 x Rated Drive
Output Power

0.01 kW

05

[Bus Voltage]

Displays the DC Bus Voltage level.

0/400 - 230V
0/800 - 460V

1 Volt

06

[Frequency Command]

Displays the frequency that the drive is commanded to output. This command
may come from any of the frequency sources selected by
P59 - [Frequency Select]

or from a currently selected preset frequency.

0.0/240.0

0.1 Hz

07

[Active Fault]

Displays the coded active fault number. If a fault is currently active (has not
been cleared) the display will flash. After fault condition is cleared, display
will read zero. Refer to P17, P18, and P19 for fault history. See Chapter 6
for fault code descriptions.

0/48

Numeric Value

08

[Heatsink Temperature]

Displays the temperature of the drive heatsink.
Note: A display value of 69 indicates a temperature of less than 70

°C.

69/150

1 Degree C

09

[Drive Status]

Displays the status of the drive in
a binary coded format.
Important:
0 = Inactive, 1 = Active.

0000/1011

Binary Number

10

[Drive Type]

Used by Rockwell Automation field service personnel.

Numeric Value

Numeric Value

11

[Firmware Version]

Displays version of drive firmware. Used by Rockwell Automation field
service personnel.

Fixed Value

Numeric Value

Bit 3

Bit 2

Bit 1

Bit 0

Running
Forward
Accel
Decel