Rockwell Automation 160 SSC Series C FRN 7.xx User Manual

Page 53

Advertising
background image

Parameters and Programming

5-15

75

[Analog Input Minimum]

Important: Do not adjust this parameter until setting P60 - [Zero Offset].
Sets the percent of analog input used to represent P32 - [Minimum Frequency].
If the minimum analog input equals minimum frequency, no action is needed. If
it is desired to adjust the analog input to equal P32 - [Minimum Frequency], use
P16 - [Analog Input] to adjust the analog input to the desired level using P60 and
then enter this value into P75.
Analog inversion can be accomplished by setting this value larger than P76.

Important: This parameter cannot be programmed while the drive is running.

0.0/150.0

0.1%

0.0%

76

[Analog Input Maximum]

Important: Do not adjust this parameter until setting P60 - [Zero Offset].
Sets the percent of analog input used to represent P33 - [Maximum Frequency].
If the maximum analog input equals maximum frequency, no action is needed. If
it is desired to adjust the analog input to equal P33 - [Maximum Frequency], use
P16 - [Analog Input] to adjust the analog input to the desired level using P60 and
then enter this value into P76.

Analog inversion can be accomplished by setting this value smaller than P75.

Important: This parameter cannot be programmed while the drive is running.

0.0/150.0

0.1%

100.0%

78

[Compensation]

Settings:

0 No compensation.
1 Some drive/motor combinations have inherent instabilities which are exhibited

as non-sinusodial motor currents. This setting attempts to correct this
condition.

2 Some motor/load combinations have mechanical resonances which can be

excited by the drive current regulator. This setting slows down the current
regulator response and attempts to correct this condition.

0 to 2

Numeric
value

0

79

[Software Current Trip]

This provides a software instantaneous current trip similar to the 300% hardware
current trip. This value is the percent above the P43 - [Current Limit] at which the
drive trips immediately. A setting of zero disables the Software Current Trip.

0/50%

1%

0%

80

[Stall Fault Time]

This selects the amount of time the drive must be in a stall condition before it
causes a stall fault.
0 = Normal stall time, approximately 60 seconds
1 = 2 times normal stall time
2 = 4 times normal stall time
3 = 6 times normal stall time
4 = 8 times normal stall time
5 = Stall fault disabled

ATTENTION: Continuous operation at high currents caused by
a stall can cause motor damage.

0/5

Numeric
Value

0

Program Group

No.

Parameter Name/Description

Min./Max.
Range

Units

Factory
Default

This parameter applies only to the Analog Signal Follower model.