Long motor cable effects, Long motor cable effects -7, See table 2.e for an e – Rockwell Automation 160 SSC Series C FRN 7.xx User Manual

Page 19

Advertising
background image

Installation and Wiring

2-7

Long Motor Cable Effects

Reflected Wave Protection

The drive should be installed as close to the motor as possible. Installations with
long motor cables may require the addition of external devices to limit voltage
reflections at the motor (reflected wave phenomena). See Table 2.E for
recommendations.

Important:

Both Reflected Wave and Capacitive Current Considerations need
to be taken into account when determining motor cable lengths
(see Table 2.E and Table 2.F). The use of an external device to
limit reflected wave phenomenon may effect the accuracy of
Bulletin 160 current sensing.

The reflected wave data applies to all frequencies 2 to 8 kHz. For 230V ratings,
the maximum cable length recommendations are the same as the capacitive current
recommendations (see Table 2.F).

Cable Length Recommendations – Reflected Wave

Table 2.E

➊ Cable lengths listed are for PWM frequencies of 2 kHz. Refer to publication 1204-5.1 for cable length recommendations at

other PWM frequencies.

➋ The maximum peak-to-peak voltage of the drive is 1400V due to the minimum on/off time software.

Reflective Wave Testing has been done on cable lengths up to 160 meters (600 feet). See Table 2.F for capacitive current
recommendations.

380-
460V
Ratings

Motor
Insulation
Rating

Motor Cable Only

RWR at Drive

Reactor at Motor

Shielded

Unshielded

Shielded

Unshielded

Shielded

Unshielded

feet

meters feet

meters feet

meters feet

meters feet

meters feet

meters

4.0 kW
(5 HP)

1000 Vp-p

45

13.7

20

6.1

525

160

600

183

325

99.1

300

91.5

1200 Vp-p

90

27.4

40

12.2

525

160

600

183

525

160

425

130

1600 Vp-p

➋ 525

160

475

145

525

160

600

183

525

160

600

183

2.2 kW
(3 HP)

1000 Vp-p

40

12.2

40

12.2

525

160

600

183

225

68.6

250

76.2

1200 Vp-p

90

27.4

60

18.3

525

160

600

183

325

99.1

425

130

1600 Vp-p

➋ 525

160

500

152

525

160

600

183

525

160

600

183

1.5 kW
(2 HP)

1000 Vp-p

40

12.2

40

12.2

425

130

600

183

325

99.1

300

91.5

1200 Vp-p

90

27.4

60

18.3

425

130

600

183

425

130

450

137

1600 Vp-p

➋ 500

152

500

152

425

130

600

183

540

165

600

183

0.75 kW
(1 HP)

1000 Vp-p

55

16.8

40

12.2

325

99.1

600

183

325

99.1

350

107

1200 Vp-p

125

38.1

60

18.3

325

99.1

600

183

500

152

450

137

1600 Vp-p

➋ 500

152

500

152

325

99.1

600

183

500

152

600

183

0.55 kW
(0.75 HP)

1000 Vp-p

45

13.7

40

12.2

300

91.5

600

183

300

91.5

300

91.5

1200 Vp-p

125

38.1

60

18.3

300

91.5

600

183

500

152

500

152

1600 Vp-p

➋ 500

152

500

152

300

91.5

600

183

500

152

600

183

0.37 kW
(0.5 HP)

1000 Vp-p

45

13.7

90

27.4

300

91.5

425

130

300

91.5

425

130

1200 Vp-p

125

38.1

180

54.9

300

91.5

425

130

500

152

500

152

1600 Vp-p

➋ 500

152

500

152

300

91.5

425

130

500

152

500

152

Advertising