Parameters and Programming

41

[Motor Overload Select

]

Bulletin 160 provides Class 10 overload protection. Settings 0 – 2 select the
derating factor for the I

2

t overload function.

0/2

Numeric
Value

0

42

[Motor Overload Current]

Set to motor nameplate Full Load Amps (FLA).

0.1/200% of
Drive Rating

0.01A

115% of
Drive
Rating

43

[Current Limit]

Maximum output current allowed before current limiting occurs. Value set in
percent of drive rated output current.

1/180% of
Drive Rating

1%

150%

44

[DC Hold Time]

The time that P45 - [DC Hold Voltage] will be applied to the motor when P34 -
[Stop Mode Select] is set to either “DC Injection Braking” or “Ramp to Stop.”

0.0/25.0

0.1
Seconds

0.0
Seconds

Program Group

No.

Parameter Name/Description

Min./Max.
Range

Units

Factory
Default

Setting

Derate Level

0

No Derate

10:1 speed range

1

Min. Derate

4:1 speed range, derate below 25% of base speed

2

Max. Derate

2:1 speed range, derate below 50% of base speed

Min Derate

0

80

100

60

40

20

% of [Overload Curent] Setting

% of [Overload Curent] Setting

% of [Overload Curent] Setting

No Derate

0

80

100

60

40

20

% of Base Speed

% of Base Speed

% of Base Speed

Max Derate

0

80

100

60

40

20

0

200

175

150

125

100

75

50

25

0

200

175

150

125

100

75

50

25

0

200

175

150

125

100

75

50

25

Settings
0 = No Derating
1 = Minimum Derating
2 = Maximum Derating