Figure 2.13 – Rockwell Automation 160 SSC Series C FRN 7.xx User Manual

Page 29

Advertising
background image

Installation and Wiring

2-17

P46 Setting 9 - Two-Wire PI Control (Analog Models Only)

This input mode is similar to Setting 1 except TB3 terminal 8 provides the function
of PI Control.

Two-Wire PI control

Figure 2.13

Refer to Chapter 5, 160 PI Control Setup for a detailed PI Control Setup description.

➊ Do not connect to TB3-5 in this mode.
➋ TB3 terminal 8 can be used to clear faults. See Figure 2.14 for details

Important:

For P46 - [Input Mode] settings 4 through 9, Terminal TB3-8 is also
used to clear faults. See figure below for details.

TB3-8 – Clear Faults

Figure 2.14

Important:

The system programmer is responsible for returning terminal
TB3-8 to its original state if necessary.

PI/Internal Frequency

56

7

8

Common


Run Forward

TB3-8 Open
PI

TB3-8 Closed
Internal Frequency

23

0 – 10V DC

Common

34

Common

4 – 20 mA

OR

TB3

TB3

TB3-8

Closed

TB3-8

Open

Fault

Occurs

Fault

Clears

Fault

Occurs

Fault

Clears