Figure 2.8, Figure 2.9 – Rockwell Automation 160 SSC Series C FRN 7.xx User Manual

Page 26

Advertising
background image

2-14

Installation and Wiring

Important:

Settings 4 through 9 provide additional flexibility of TB3 control
input terminal 8.

P46 Setting 4 - Two-Wire Accel/Decel Control

This input mode is similar to Setting 1 except TB3 terminal 8 provides the function
of switching from P30 - [Accel Time 1] and P31 - [Decel Time 1] to P69 - [Accel Time 2]
and P70 - [Decel Time 2] for any commanded frequency reference.

Two-Wire Accel/Decel control

Figure 2.8

➊ TB3 terminal 8 can be used to clear faults. See Figure 2.14 for details.

P46 Setting 5 - Two-Wire Enable Control

This input mode is similar to Setting 1 except TB3 terminal 8 provides the function
of “enable” command. The “enable” input is required for the drive to operate and
if opened during operation the programmed P34 - [Stop Mode] will be overridden
and the motor will coast to rest.

Two-Wire Enable control

Figure 2.9

➊ TB3 terminal 8 can be used to clear faults. See Figure 2.14 for details.
➋ When this input is in an open state, the motor will coast to rest.

56

7

8

Run Reverse

Run Forward

Common

Accel/Decel Select

TB3

TB3-8 Open
Accel 2, Decel 2

TB3-8 Closed
Accel 1, Decel 1

Enable

56

7

8

Common

Run Reverse

Run Forward

TB3

TB3-8 Open
Controller Disabled

TB3-8 Closed
Controller Enabled