5-4

Parameters and Programming

Display Group (Read Only)

No.

Parameter Name/Description

Min./Max. Range

Units

12

[Input Status]

Displays the open (0) and closed (1) state of the inputs to TB3 in binary coded
format as follows:

0000/1111

Binary Number

13

[Power Factor Angle]

Displays the angle in electrical degrees between motor voltage and motor current.

0.0/180.0

0.1 degrees

14

[Memory Probe Display]

Used by Rockwell Automation field service personnel.

Numeric Value

Numeric Value

15

[Preset Status]

Displays the open (0) and closed (1)
state of TB3 inputs SW1, SW2 and
SW3 in binary coded format.

Preset –
0000/0111

Analog –
0000/0011

Binary Number

16

[Analog Input]

Displays the analog input as a percent of full scale. Used in setting P60 - [Zero
Offset], P75 - [Analog Input Minimum], and P76 - [Analog Input Maximum].

Important: On initial set up of the drive, apply a 0V or 4 mA analog command to

the drive. Once applied, if the value of this parameter displays
something other than zero, program that value into P60 - [Zero Offset].
Please note that the value of [Zero Offset] will be subtracted from the
value of this parameter.

–150.0/+150.0

0.1%

Bit 3
Polarity

Bit 2
TB3-6

Bit 1
TB3-8

Bit 0
TB3-5

Input Mode 0
(3-Wire)

0 =
Positive
Analog
Input

1 =
Negative
Analog
Input

Start

Stop

Reverse

Input Mode 1
(2-Wire)

Run
Forward

Stop

Run
Reverse

Input Mode 2
(Keypad)

N/A

Stop

N/A

Input Mode 3
(Mom. Run Fwd./Rev.)

Run
Forward

Stop

Run
Reverse

Input Mode 4
(Accel/Decel)

Run
Forward

0 = Accel 2/Decel 2
1 = Accel 1/Decel 1

Run
Reverse

Input Mode 5
(Coast to Rest)

Run
Forward

Coast to Rest Stop

Run
Reverse

Input Mode 6
(TB3 Control/
Keypad or Comm.)

Run
Forward

0 = TB3 Control
1 = Keypad or Comm.

Run
Reverse

Input Mode 7
(Frequency Select)

Run
Forward

0 = Analog Frequency Select
1 = Internal Frequency Select

Run
Reverse

Input Mode 8

(SF1 Preset Speed)

Run
Forward

0 = Open
1 = Closed

Run
Reverse

Input Mode 9
(2-Wire PI control)

Run
Forward

0 = PI
1 = Internal Frequency Select

Run
Reverse

Status of Bit 3 for Input Mode 8 is TB3-2 is: 0 = Open, 1 = Closed.

SW1
SW2
SW3
Not Used

Bit 3

Bit 2

Bit 1

Bit 0

This parameter applies only to the Analog Signal Follower model.

This TB3 input applies only to the Preset Speed model.