5-10

Parameters and Programming

47

[Output Configure]

Configures the TB3 relay output functionality.

0/10

Numeric
Value

0

48

[Output Threshold]

Determines the on/off point for the TB3 output relay when P47 - [Output Configure]
is set to 6, 7, 8, and 10.

Setting

Ranges

6

0 to 240 Hz

7

0 to 180%

8

0 to 815 Volts

10

0 to 180˚

0/815

Numeric
Value

0

49

[PWM Frequency]

Carrier frequency for the PWM output waveform. The chart below provides
derating guidelines based on the PWM frequency setting.

Important: Ignoring derating guidelines can cause reduced drive performance.

2.0/8.0

0.1 kHz

4.0 kHz

50

[Restart Tries]

Maximum number of times the drive will attempt to reset a fault.
Faults 03 – 20 will automatically reset according to this parameter setting.

0/9

Numeric
Value

0

Program Group

No.

Parameter Name/Description

Min./Max.
Range

Units

Factory
Default

Setting

Output Changes State When . . .

0

Drive Ready/Faulted

Energized and returns to shelf state when power is
removed or a fault occurs.

1

At Frequency

Drive reaches commanded frequency.

2

Motor Running

The motor is receiving power from drive.

3

Reverse

Drive is commanded to run in the reverse direction.

4

Motor Overload

A motor overload condition exists.

5

Ramp Regulated

The ramp regulator is modifying the programmed accel/
decel times to avoid an overcurrent or overvoltage fault
from occurring.

6

Above Frequency

The drive exceeds the frequency value set in
P48 - [Output Threshold].

7

Above Current

Drive exceeds the value set in P48 - [Output Threshold].
Important: Value for P48 - [Output Threshold] must be
entered in percent of drive rated output current.

8

Above DC Bus Voltage

Drive exceeds the DC bus voltage value set in
P48 - [Output Threshold].

9

Retries Exhausted

Number of retries for P50 - [Restart Tries] is exceeded.

10

Above Power Factor
Angle

Power Factor angle exceeds the value set in
P48 - [Output Threshold].

1

2

3

4

5

6

7

8

84

86

88

90

92

94

96

98

100

% Output Current (A)

Carrier Frequency (kHz)