5-10 Using Trim Pots and the Data Access Tool (DAT)

DAT Error Codes

Error Code

Description

Caused by

Recommended Action

00

Interface time-out

Communication traffic

Add SVC instructions to ladder program

01 to 02

Power-up test failure

Internal failure

Remove and re-insert the DAT. If failure
persists, replace the unit.

03 to 07

internal error

Internal failure

Remove and re-insert the DAT. If failure
persists, replace the unit.

08

processor owned

(1)

Another device has ownership of the controller

Release ownership by the other device

09

access denied

Cannot access that file because another device
has ownership

Release file ownership by the other device

31 to 34

internal error

Internal failure

Remove and re-insert the DAT. If failure
persists, replace the unit.

(1) This error can occur after a download in which communications configurations are changed. This error can be cleared by removing and re-installing the DAT, or by cycling

power to the controller.