Wiring diagrams, Wiring diagrams -8, Miswiring - 1764-28bxb only -8 – Rockwell Automation 1764-xxxx MICROLOGIX 1500 PROGRAMMABLE CONTROLLERS User Manual

Page 58

Advertising
background image

Publication 1764-UM001B-EN-P - April 2002

3-8 Wiring Your Controller

Wiring Diagrams

This section shows the wiring diagrams for the MicroLogix 1500
controllers. Controllers with dc inputs can be wired as either sinking
or sourcing configuration. (Sinking and sourcing does not apply to ac
inputs.) See pages 3-12 through 3-15 for sinking and sourcing wiring
diagrams.

Miswiring - 1764-28BXB Only

The following table shows miswiring conditions and the
consequences of improper wiring:

TIP

This

symbol denotes a protective earth ground

terminal which provides a low impedance path
between electrical circuits and earth for safety
purposes and provides noise immunity improvement.
This connection must be made for safety purposes.

Condition

Result

Operating with Voltage
Less than 20.4V dc

This will not damage the base unit. The base unit may not
power up.

IMPORTANT

This is not recommended. You must
verify that the line voltage remains
within specified limits.

Reverse Wiring of the Line
Terminals (0 to 30V dc)

Reverse wiring will not damage the base unit. The base unit
will not power up.

Applied Voltage Level
Exceeds the Published
Recommended Value
(i.e. applying 120V ac to
240V ac)

Exceeding the published recommended voltage may result
in permanent damage to the base unit.