Communication Connections 4-3

Connecting to the RS-232
Port

DF1 Full-Duplex Communication Parameters

When a communication channel is configured for DF1 Full-Duplex,
the following parameters can be changed.

Making a DF1 Full-Duplex Point-to-Point Connection

You can connect the MicroLogix 1500 programmable controller to
your personal computer using a serial cable from your personal
computer’s serial port to the controller, as shown in the illustrations
below.

Table 4.2 DF1 Full-Duplex Configuration Parameters

Parameter

Options

Default

Baud Rate

300, 600, 1200, 2400, 4800, 9600, 19.2K, 38.4K 19.2K

Parity

none, even

none

Source ID (Node
Address)

0 to 254 decimal

1

Control Line

no handshaking, Full-Duplex modem
handshaking

no
handshaking

Error Detection

CRC, BCC

CRC

Embedded Responses

auto-detect, enabled

auto detect

Duplicate Packet
(Message) Detect

enabled, disabled

enabled

ACK Timeout

1 to 65535 counts (20 ms increments)

50 counts

NAK retries

0 to 255

3 retries

ENQ retries

0 to 255

3 retries

Stop Bits

not a setting, always 1

1

ATTENTION

!

Chassis ground, internal 24V ground, user 24V dc
ground, and RS-232 ground are internally connected.
You must connect the chassis ground terminal screw
to ground prior to connecting any devices. It is
important that you understand your personal
computer’s grounding system before connecting to
the controller. An optical isolator, such as the
1761-NET-AIC, is recommended between the
controller and your personal computer when using
Channel 0. An isolator is not required when using
Channel 1 (1764-LRP).