F1 and f2 functions -7 working screen operation -7, F1 and f2 functions, Working screen operation – Rockwell Automation 1764-xxxx MICROLOGIX 1500 PROGRAMMABLE CONTROLLERS User Manual

Page 99

Advertising
background image

Publication 1764-UM001B-EN-P - April 2002

Using Trim Pots and the Data Access Tool (DAT) 5-7

5. Press ENTER to load the new data. Press ESC or INT/BIT to

discard the new data.

F1 and F2 Functions

The function keys, F1 and F2, correspond to bits and can be used
throughout the control program as desired. They have no effect on bit
or integer monitoring.

Each key has two corresponding bits in the DAT function file. The bits
within the DAT function file are shown in the table below.

F1 or F2 Key Pressed

The pressed bits (DAT:0/F1P and DAT:0/F2P) function as
push-buttons and provide the current state of either the F1 or F2 key
on the keypad. When the F1 or F2 key is pressed, the DAT sets (1) the
corresponding pressed key bit. When the F1 or F2 key is not pressed,
the DAT clears (0) the corresponding pressed key bit.

F1 or F2 Key Latched

The latched bits (DAT:0/F1L and DAT:0/F2L) function as latched
push-buttons and provide latched/toggle key functionality. When the
F1 or F2 key is pressed, the DAT sets (1) the corresponding latched
key bit within the DAT Function File. When the F1 or F2 key is
pressed a second time, the DAT clears (0) the corresponding latched
key bit.

Working Screen Operation

Because the DAT is a communications device, its performance is
affected by the scan time of the controller. Depending on the user
program, if a long scan time is encountered and the DAT waits for
information from the controller, a working screen is displayed. The

Key

Bits

Address

Data Format

Type

User Program
Access

F1 Key

Pressed

DAT:0/F1P

Binary

Status

Read/Write

Latched

DAT:0/F1L

Binary

Status

Read/Write

F2 Key

Pressed

DAT:0/F2P

Binary

Status

Read/Write

Latched

DAT:0/F2L

Binary

Status

Read/Write