Publication 1764-UM001B-EN-P - April 2002

Specifications A-5

IMPORTANT

The relay current must stay within the limits defined
in Tables A.5 and A.6.

Table A.5 Relay Contact Rating Table 1764-24AWA, -24BWA, -28BXB

Maximum
Volts

Amperes

Amperes
Continuous

Voltamperes

Make

Break

Make

Break

240V ac

7.5A

0.75A

2.5A

1800VA

180VA

(2)

(2) The total load controlled by the 1764-24AWA and 1764-24BWA is limited to 1440VA (break).

120V ac

15A

1.5A

125V dc

0.22A

(1)

(1) For dc voltage applications, the make/break ampere rating for relay contacts can be determined by dividing 28

VA by the applied dc voltage. For example, 28 VA/48V dc = 0.58A. For dc voltage applications less than 14V, the
make/break ratings for relay contacts cannot exceed 2A.

1.0A

28VA

24V dc

1.2A

(1)

2.0A

28VA

Table A.6 Output Specifications - Maximum Continuous Relay Current

Specification

1764-24AWA,
-24BWA

1764-28BXB

Current per Common

8A

8A

Current per
Controller

at 150V Maximum

24A

18A

at 240V Maximum

20A

18A

Table A.7 1764-28BXB FET Output Specifications

Specification

General
Operation
(Outputs 2 thru 7)

High Speed
Operation

(1)

(Outputs 2 and 3 Only)

User Supply
Voltage

minimum

20.4V dc

20.4V dc

maximum

26.4V dc

26.4V dc

On-State
Voltage Drop

at maximum load
current

1V dc

Not Applicable

at maximum surge
current

2.5V dc

Not Applicable

Current Rating
per Point

maximum load

1A at 55°C (131°F)
1.5A at 30°C (86°F)

100 mA

minimum load

1.0 mA

10 mA

maximum leakage

1.0 mA

1.0 mA