Rockwell Automation 1764-xxxx MICROLOGIX 1500 PROGRAMMABLE CONTROLLERS User Manual

Page 111

Advertising
background image

Publication 1764-UM001B-EN-P - April 2002

Specifications A-3

Figure 1.2 Input Power Required

Table A.2 Input Specifications

Description

1764-24AWA

1764-24BWA and 1764-28BXB

Inputs 0 thru 7

Inputs 8 and
Higher

On-State Voltage
Range

79 to 132V ac

14 to 30.0V dc at
30°C (86°F)
14 to 26.4V dc at
55°C (131°F)

10 to 30.0V dc at
30°C (86°F)
10 to 26.4V dc at
55°C (131°F)

Off-State Voltage
Range

0 to 20V ac

0 to 5V dc

Operating
Frequency

Not Applicable

1 kHz to 20 kHz

1 kHz to 500 Hz

(1)

(1) Scan-time dependant.

On-State Current:

minimum

nominal

maximum

5.0 mA at 79V ac

12.0 mA at 120V ac

16.0 mA at 132V ac

2.5 mA at 14V dc

7.3 mA at 24V dc

12.0 mA at 30V dc

2.0 mA at 10V dc

8.9 mA at 24V dc

12.0 mA at 30V dc

Off-State Leakage
Current

2.5 mA minimum

1.5 mA minimum

Nominal
Impedance

12k ohms at 50 Hz
10k ohms at 60 Hz

3.3k ohms

2.7k ohms

Inrush Current
(max.)

250 mA at 120V ac

Not Applicable

Not Applicable

TIP

The 1764-24AWA input circuits (inputs 0-11) do not
support adjustable filter settings. They have
maximum turn-on and maximum turn-off times of
20 milliseconds.

0

5

10

15

20

25

30

0

2

4

6

8

10

12

14

16

18

Input

Powe

r Re

qui

red (W

at

ts

)

Power Consumption (Watts)