Table A.3 Response Times for High-Speed dc Inputs 0 Through 7
(applies to 1764-24BWA and 1764-28BXB)

Maximum
High-Speed Counter
Frequency at 50%
Duty Cycle (KHz)

Filter
Setting
(ms)

Minimum
ON Delay
(ms)

Maximum
ON Delay
(ms)

Minimum
OFF Delay
(ms)

Maximum
OFF Delay
(ms)

20.000

0.025

0.005

0.025

0.005

0.025

6.700

0.075

0.040

0.075

0.045

0.075

5.000

0.100

0.050

0.100

0.060

0.100

2.000

0.250

0.170

0.250

0.210

0.250

1.000

0.500

0.370

0.500

0.330

0.500

0.500

1.000

0.700

1.000

0.800

1.000

0.250

2.000

1.700

2.000

1.600

2.000

0.125

4.000

3.400

4.000

3.600

4.000

0.063

8.000

(1)

(1) This is the default setting.

6.700

8.000

7.300

8.000

0.031

16.000

14.000

16.000

14.000

16.000

Table A.4 Response Times for Normal dc Inputs 8 Through 11 (1764-24BWA)
and 8 Through 15 (1764-28BXB)

Maximum
Frequency at 50%
Duty Cycle (kHz)

Filter
Setting
(ms)

Minimum
ON Delay
(ms)

Maximum
ON Delay
(ms)

Minimum
OFF Delay
(ms)

Maximum
OFF Delay
(ms)

1.000

0.500

0.090

0.500

0.020

0.500

0.500

1.000

0.500

1.000

0.400

1.000

0.250

2.000

1.100

2.000

1.300

2.000

0.125

4.000

2.800

4.000

2.700

4.000

0.063

8.000

(1)

(1) This is the default setting.

5.800

8.000

5.300

8.000

0.031

16.000

11.000

16.000

10.000

16.000

Advertising