Rockwell Automation 1764-xxxx MICROLOGIX 1500 PROGRAMMABLE CONTROLLERS User Manual

Page 115

Advertising
background image

Publication 1764-UM001B-EN-P - April 2002

Specifications A-7

Table A.8 Working Voltage (1764-24AWA)

Specification

1764-24AWA

Power Supply Input to Backplane
Isolation

Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second

265V Working Voltage (IEC Class 2 reinforced
insulation)

Input Group to Backplane
Isolation and Input Group to
Input Group Isolation

Verified by one of the following dielectric tests: 151V
ac for 1 second or 2145V dc for 1 second

132V Working Voltage (IEC Class 2 reinforced
insulation)

Output Group to Backplane
Isolation

Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second

265V Working Voltage (IEC Class 2 reinforced
insulation)

Output Group to Output Group
Isolation

Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second

265V Working Voltage (basic insulation) 150V Working
Voltage (IEC Class 2 reinforced insulation).

Table A.9 Working Voltage (1764-24BWA)

Specification

1764-24BWA

Power Supply Input to Backplane
Isolation

Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second

265V Working Voltage (IEC Class 2 reinforced
insulation)

Power Supply User 24V Output
to Backplane Isolation

Verified by one of the following dielectric tests: 600V
ac for 1 second or 848V dc for 1 second

50V Working Voltage (IEC Class 2 reinforced insulation)

Input Group to Backplane
Isolation and Input Group to
Input Group Isolation

Verified by one of the following dielectric tests: 1200V
ac for 1 second or 1697V dc for 1 second

75V dc Working Voltage (IEC Class 2 reinforced
insulation)

Output Group to Backplane
Isolation

Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second

265V Working Voltage (IEC Class 2 reinforced
insulation).

Output Group to Output Group
Isolation.

Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second

265V Working Voltage (basic insulation) 150V Working
Voltage (IEC Class 2 reinforced insulation)

Advertising