A-8 Specifications

Transistor Output Transient Pulses

Refer to page 3-16 for “Transistor Output Transient Pulses”.

Table A.10 Working Voltage (1764-28BXB)

Specification

1764-28BXB

Input Group to Backplane
Isolation and Input Group to
Input Group Isolation

Verified by one of the following dielectric tests: 1200V
ac for 1 second or 1697V dc for 1 second

75V dc Working Voltage (IEC Class 2 reinforced
insulation)

FET Output Group to Backplane
Isolation and FET Outputs Group
to Group

Verified by one of the following dielectric tests: 1200V
ac for 1 second or 1697V dc for 1 second

75V dc Working Voltage (IEC Class 2 reinforced
insulation)

Relay Output Group to
Backplane Isolation

Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second

265V Working Voltage (IEC Class 2 reinforced
insulation)

Relay Output Group to Relay and
FET Output Group Isolation

Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second

265V Working Voltage (basic insulation) 150V Working
Voltage (IEC Class 2 reinforced insulation)