Sinking and sourcing input circuits, Terminal groupings -10, Sinking and sourcing input circuits -10 – Rockwell Automation 1764-xxxx MICROLOGIX 1500 PROGRAMMABLE CONTROLLERS User Manual

Page 60

Advertising
background image

Publication 1764-UM001B-EN-P - April 2002

3-10 Wiring Your Controller

Terminal Groupings

Sinking and Sourcing Input
Circuits

Any of the MicroLogix 1500 DC embedded input groups can be
configured as sinking or sourcing depending on how the DC COM is
wired on the group. See pages 3-12 through 3-15 for sinking and
sourcing wiring diagrams.

Controller

Inputs
Input Group

Common Terminal

Input Terminal

1764-24BWA

Group 0

DC COM 0

I/0 through I/3

Group 1

DC COM 1

I/4 through I/7

Group 2

DC COM 2

I/8 through I/11

1764-24AWA

Group 0

AC COM 0

I/0 through I/3

Group 1

AC COM 1

I/4 through I/7

Group 2

AC COM 2

I/8 through I/11

1764-28BXB

Group 0

DC COM 0

I/0 through I/3

Group 1

DC COM 1

I/4 through I/7

Group 2

DC COM 2

I/8 through I/15

Controller

Outputs
Output Group

Voltage Terminal

Output Terminal

1764-24BWA

Group 0

VAC/VDC 0

O/0

Group 1

VAC/VDC 1

O/1

Group 2

VAC/VDC 2

O/2

Group 3

VAC/VDC 3

O/3

Group 4

VAC/VDC 4

O/4 through O/7

Group 5

VAC/VDC 5

O/8 through O/11

1764-24AWA

Group 0

VAC/VDC 0

O/0

Group 1

VAC/VDC 1

O/1

Group 2

VAC/VDC 2

O/2

Group 3

VAC/VDC 3

O/3

Group 4

VAC/VDC 4

O/4 through O/7

Group 5

VAC/VDC 5

O/8 through O/11

1764-28BXB

Group 0

VAC/VDC 0

O/0

Group 1

VAC/VDC 1

O/1

Group 2

VDC 2, VDC COM 2

O/2 through O/7

Group 3

VAC/VDC 3

O/8 and O/9

Group 4

VAC/VDC 4

O/10 and O/11

Type

Definition

Sinking Input
connection of a PNP sourcing device

The input energizes when high-level voltage is
applied to the input terminal (active high). Connect
the power supply VDC (-) to the DC COM terminal.

Sourcing Input
connection of an NPN sinking device

The input energizes when low-level voltage is
applied to the input terminal (active low). Connect
the power supply VDC (+) to the DC COM terminal.