Publication 1764-UM001B-EN-P - April 2002

System Loading and Heat Dissipation F-7

System Using a 1769-PA4

To validate your system, the total 5V dc current and 24V dc current
consumed must be considered. The I/O modules connected to the
PB2 should be distributed, such that the current consumed from the
left and right side of the power supply never exceeds 2A at 5V and
0.8A at 24V dc with an ambient temperature of 0 to 55

°

C. Use the

current graph below to determine if the power supply loading in your
system is:

within the allowable range for special load conditions

above 55

°

to 60

°

C.

Figure 7 1769-PA4 5V and 24V dc Current

System Using a 1769-PB4

To validate your system, the total 5V dc current and 24V dc current
consumed must be considered. The I/O modules connected to the
PB2 should be distributed, such that the current consumed from the
left and right side of the power supply never exceeds 2A at 5V and
0.8A at 24V dc with an ambient temperature of 0 to 55

°

C. Use the

current graph below to determine if the power supply loading in your
system is:

within the allowable range for special load conditions

above 55

°

to 60

°

C.

4.0

3.0

2.0

1.0

0.0

0.0

0.2

0.4

0.6

0.8

1.0

1.2

60˚C

1.4

1.6

1.8

2.0

2.6

1.7

55˚C

4.0

3.0

2.0

1.0

0.0

0.0

0.2

0.4

0.6

0.8

1.0

1.2

60˚C

1.4

1.6

1.8

2.0

2.6

1.7

55˚C

+24V Bus Load (Amps)

+5V

B

us

Load

(A

mp

s)

Total Output: 68W at 55°C or below 61W at 60°C or below