1-8 Hardware Overview

To support a maximum of 16 I/O modules in an additional I/O bank,
you must have the following:

Table 1.4 Requirements to Support a Maximum of 16 I/O Modules

Product

Catalog Number

MicroLogix 1500 Processor

1764-LSP, Series C or higher
1764-LRP, Series C or higher

MicroLogix 1500 Base Unit

1764-24AWA, Series B or higher
1764-24BWA, Series B or higher
1764-28BXB, Series B or higher

Operating System Version

Firmware Revision Number (FRN) 6 or higher

(1)

(1) You can check the FRN by looking at word S:59 (Operating System FRN) in the Status File.

Programming Software

RSLogix 500, Version 5.10.00 or higher.

1 Power Supply (optional)

1769-PA2, 1769-PA4, 1769-PB2, 1769-PB4

1 Cable (optional)

1769-CRL1, 1769-CRL3, 1769-CRR1, 1769-CRR3

1 End Cap (required)

1769-ECL, 1769-ECR

IMPORTANT

If your processor is at an older revision, you must
upgrade the operating system to FRN 3 or higher
to use an expansion cable and power supply (or to
FRN 6 or higher to allow up to 16 expansion
modules). On the Internet, go to
http://www.ab.com/micrologix to download the
operating system upgrade. Navigate to MicroLogix
1500 for further instructions and downloads.

MicroLogix 1500 base units are not field upgradeable
from Series A to Series B.