Schematic (using iec symbols) -10, Schematic (using iec symbols) – Rockwell Automation 1764-xxxx MICROLOGIX 1500 PROGRAMMABLE CONTROLLERS User Manual

Page 36

Advertising
background image

Publication 1764-UM001B-EN-P - April 2002

2-10 Installing Your Controller

Schematic (Using IEC Symbols)

Disconnect

Isolation
Transformer

Emergency-Stop
Push Button

Fuse

MCR

230V ac
I/O
Circuits

Operation of either ofthese contacts will
remove power from the external I/O
circuits, stopping machine motion.

Fuse

Overtravel
Limit Switch

MCR

MCR

MCR

Stop

Start

Line Terminals:
Connect to terminals of Power Supply
(1764-24AWA and 1764-24BWA).

115V ac or
230V ac
I/O Circuits

L1

L2

230V ac

Master Control Relay (MCR)
Cat. No. 700-PK400A1

Suppressor
Cat. No.
700-N24

MCR

Suppr.

24V dc
I/O
Circuits

(Lo)

(Hi)

dc Power Supply.
Use IEC 950/EN 60950

X1

X2

115V ac

or 230V ac

Line Terminals: Connect to 24V dc
terminals of Power Supply.

_

+

Advertising