Publication 1764-UM001B-EN-P - April 2002

System Loading and Heat Dissipation F-5

System Using a 1769-PA2

To validate your system, the total 5V dc current and 24V dc current
consumed must be considered. The I/O modules must be distributed,
such that the current consumed from the left or right side of the
power supply never exceeds 2A at 5V dc and 1.0A at 24V dc. Use the
current graphs below to determine if the power supply loading in
your system is within the allowable range.

Figure F.1 1769-PA2 Current with +24V dc User Load = 0A

Table F.5 Bank 1 Power Supply Loading - Verify the Current Limits

Specification

Catalog Number

Calculated Current for System

24V dc User Output
Capacity

at 5V dc (mA)

at 24V dc (mA)

Values from SUBTOTAL2 (Table F.2):

(C)

(D)

MAXIMUM CURRENT LIMIT

1769-PA2

2000

800

250 mA

1769-PA4

4000

2000

n/a

1769-PB2

2000

800

1769-PB4

4000

2000

I/O Distribution - Distribute I/O modules
such that the current consumed from either
the left side or the right side of the power
supply never exceeds the following values:

1769-PA2

2000

800

250 mA

1769-PA4

2000

1000

n/a

1769-PB2

2000

800

1769-PB4

2000

1000

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

0.0

0.5

1.0

1.5

2.0

+5

V

d

c

L

o

ad

(

A

m

p

s)

+24V dc Load (Amps)

Valid Operating Range