Using Real-Time Clock and Memory Modules 6-3

Use the Disable Clock button in your programming device to disable
the real-time clock before storing a module. This decreases the drain
on the battery during storage.

Memory Module Operation

The memory module supports program back-up as well as the
following features:

User Program and Data Back-Up

Program Compare

Data File Download Protection

Memory Module Write Protection

Removal/Insertion Under Power

User Program and Data Back-Up

The memory module provides a simple and flexible program/data
transport mechanism, allowing the user to transfer the program and
data to the controller without the use of a personal computer and
programming software.

The memory module can store one user program at a time.

During transfers from a memory module, the controller’s RUN LED
flashes.

Table 6.1 RTC Battery Life Expectancy

Battery State

Temperature

Time Duration

Operating

0°C to +40°C (+32°F to +104°F)

5 years

(1)

(1) The operating life of the battery is based on 6 months of storage time before the real-time clock is used.

Storage

-40°C to +25°C (-40°F to +77°F)

5 years minimum

+26°C to +60°C (+79°F to +140°F)

3 years minimum

ATTENTION

!

Operating with a low battery indication for more
than 14 days may result in invalid RTC data if
controller power is lost.