Multiple cable connection, Grounding and terminating the dh-485 network – Rockwell Automation 1764-xxxx MICROLOGIX 1500 PROGRAMMABLE CONTROLLERS User Manual

Page 82

Advertising
background image

Publication 1764-UM001B-EN-P - April 2002

4-14 Communication Connections

Multiple Cable Connection

When connecting multiple cables to the DH-485 connector, use the
following diagram.

Grounding and Terminating the DH-485 Network

Only one connector at the end of the link must have Terminals 1 and
2 jumpered together. This provides an earth ground connection for
the shield of the communication cable. Both ends of the network must
have Terminals 5 and 6 jumpered together, as shown below. This
connects the termination impedance (of 120

) that is built into each

AIC+ as required by the DH-485 specification.

Table 4.6 Connections using Belden #3106A Cable

For this Wire/Pair

Connect this Wire

To this Terminal

Shield/Drain

Non-jacketed

Terminal 2 - Shield

Blue

Blue

Terminal 3 - (Common)

White/Orange

White with Orange
Stripe

Terminal 4 - (Data B)

Orange with White
Stripe

Terminal 5 - (Data A)

Table 4.7 Connections using Belden #9842 Cable

For this Wire/Pair

Connect this Wire

To this Terminal

Shield/Drain

Non-jacketed

Terminal 2 - Shield

Blue/White

White with Blue Stripe

Cut back - no
connection

(1)

(1) To prevent confusion when installing the communication cable, cut back the white with blue stripe wire

immediately after the insulation jacket is removed. This wire is not used by DH-485.

Blue with White Stripe

Terminal 3 -
(Common)

White/Orange

White with Orange
Stripe

Terminal 4 - (Data B)

Orange with White
Stripe

Terminal 5 - (Data A)

to Next Device

to Previous Device