3 - wiring your controller, Wiring requirements, Chapter 3 – Rockwell Automation 1764-xxxx MICROLOGIX 1500 PROGRAMMABLE CONTROLLERS User Manual

Page 51: Wiring your controller, Wiring requirements -1, Chapter

Advertising
background image

1

Publication 1764-UM001B-EN-P - April 2002

Chapter

3

Wiring Your Controller

This chapter describes how to wire your controller. Topics include:

wiring requirements

using surge suppressors

grounding guidelines

sinking and sourcing circuits

wiring diagrams, input voltage ranges, and output voltage
ranges

minimizing noise

Wiring Requirements

Wire Type

Wire Size

(1)

(1) Two wires maximum per terminal screw.

Wiring Torque

Solid

Cu-90°C (194°F)

#14 to #22 AWG

1.13 Nm (10 in-lb) rated
1.3 Nm (12 in-lb) maximum

Stranded

Cu-90°C (194°F)

#14 to #22 AWG

ATTENTION

!

Be careful when stripping wires. Wire fragments that
fall into the controller could cause damage. Once
wiring is complete, be sure the base unit is free of all
metal fragments before removing protective debris
strips and installing the processor unit. Failure to
remove strips before operating can cause
overheating.