Hardware Overview 1-7

Expansion Power Supply and Cables

With Operating System Revision Number (FRN) 3 or higher, you can
connect an additional bank of I/O to your controller. Using an
expansion power supply increases the system’s capacity for adding
expansion I/O modules. The additional I/O bank is connected to the
controller via a specially designed cable. The additional I/O bank
must include a power supply and an end cap.

System Requirements for Using Expansion Modules

To support a maximum of 8 I/O modules in an additional I/O bank,
you must have the following:

TIP

Depending on the system configuration, each
controller can support up to 16 expansion I/O
modules. See the System Requirements for Using
Expansion Modules be
low. Also see System
Guidelines on page 1-9 f
or system limitations and
illustrations of expansion I/O banks.

Table 1.3 Requirements to Support a Maximum of 8 I/O Modules

Product

Catalog Number

MicroLogix 1500
Processor

1764-LSP, Series A, Revision C or higher
1764-LSP, Series B or higher
1764-LRP, Series B or higher

MicroLogix 1500
Base Unit

1764-24AWA, Series A or higher
1764-24BWA, Series A or higher
1764-28BXB, Series A or higher

Operating System
Version

Firmware Revision Number (FRN) 3 or higher

(1)

(1) You can check the FRN by looking at word S:59 (Operating System FRN) in the Status File.

Programming
Software

1764-LSP, Series A

RSLogix 500, Version 3.01.09 or higher,

1764-LSP, Series B
1764-LRP, Series B

RSLogix 500, Version 4.00.00 or higher.

1764-LSP, Series C
1764-LRP, Series C

RSLogix 500, Version 5.00.00 or higher.

1 Power Supply
(optional)

1769-PA2, 1769-PA4
1769-PB2, 1769-PB4

1 Cable (optional)

1769-CRL1, 1769-CRL3, 1769-CRR1, 1769-CRR3

1 End Cap (required)

1769-ECL, 1769-ECR