Publication 1764-UM001B-EN-P - April 2002

F-4 System Loading and Heat Dissipation

Verifying the System Loading

To have a valid system, both current and power requirements must be
satisfied.

Verifying the Base Unit Loading

1. Enter the SUBTOTAL values from Tables F.1 and F.2. Add the

total current draw for the Base Unit. Verify the values are within
the maximum limits.

2. Using the table below, verify that the MAXIMUM POWER LIMIT

is not exceeded.

Verifying the Expansion Power Supply Loading

Using the values from SUBTOTAL2, verify that the system loading and
I/O distribution are within the limits shown in Table F.5. Consider
future expansion when selecting a power supply.

Table F.3 Base Unit Power Supply Loading - Verify the Current Limits

Current from:

Calculated Current for System

at 5V dc (mA)

at 24V dc (mA)

For 1764-24BWA only, enter sum of any User 24V dc Sensor Current

(E)

MAXIMUM LIMIT

n/a

400 mA User 24V dc

Values from SUBTOTAL1 (Table F.1)

(A1)

(B1)

Values from SUBTOTAL2 (Table F.2)

(A2)

(B2)

TOTAL BASE UNIT CURRENT LOADING

(F)

(G)

MAXIMUM LIMIT

2250 mA at 5V dc

400 mA at 24V dc

Table F.4 Base Unit Power Supply Loading - Verify the Required Power

Catalog Number:

1764-24AWA, 1764-28BXB Base Units

1764-24BWA Base Unit

5V Power Calculation

(F)

x 5V

= W

(F)

x 5V

= W

24V Power Calculation

(G)

x 24V

= W

(G)

x 24V

= W

(E)

x 24V

= W

Add up Total Watts

W

W

MAXIMUM POWER
LIMIT

16W

22W